Quartz‐Enhanced Photoacoustic Spectroscopy Sensor for Detection of Dissolved Carbon Monoxide in Transformer Oil

View at publisher
Authors: Bing Luo, Jialiang Dai, Gang Wang, H D Zhang, Wei Xiao, Zheng Zhong, Y. H. Chen, Chaofan Feng, Ruyue Cui, Lei Dong, Hongpeng Wu
Cited by: 3
References: 46

Abstract

ABSTRACT In this paper, we proposed a quartz‐enhanced photoacoustic spectroscopy (QEPAS) sensor system for detecting dissolved carbon monoxide (CO) in transformer oil. The sensor system was designed to be highly sensitive, compact, and cost‐effective. An on‐beam configured acoustic micro‐resonator (AmR) coupled with a quartz tuning fork functions as an acoustic transducer to enhance photoacoustic signals. This sensor system achieved a minimum detection limit (MDL) of 0.37 ppm for CO based on the absorption line with a wavelength of 2333.72 nm. This value is three orders of magnitude lower than the safety threshold specified in relevant standards for dissolved gas detection in transformer oil. The proposed method offered high sensitivity, low cost, a compact form factor, and ease of integration, offering a novel technical solution for dissolved gas detection in transformer oil.

Fields of Study & Subjects

Spectroscopy and Laser Applications Gas Sensing Nanomaterials and Sensors Photoacoustic and Ultrasonic Imaging

Publication details

Journal / source
Microwave and Optical Technology Letters
Publisher
Wiley
Volume
68
Issue
1
Publication date
1 January 2026