Probing armour losses formulae from CIGRE technical Brochure 908

Read full text
Authors: Pasquale Cambareri, Luca Di Rienzo, Carlo Fiorito de Falco, Massimo Bechis
Cited by: 0
References: 7

Abstract

Abstract This paper probes the validity up to 15 kHz of the analytical formulae published in the CIGRE Technical Brochure 908 related to the calculation of the armour losses in single-armoured AC cables, which have been tested in the Brochure at 50 Hz only. After briefly reviewing the theoretical background and carefully explaining the approximations performed by the Brochure, it is shown that for a typical cable, the analytical formulae are reasonably accurate in the estimation of losses up to 15 kHz, but the absolute error increases linearly with frequency.

Fields of Study & Subjects

Thermal Analysis in Power Transmission High voltage insulation and dielectric phenomena Electrical Fault Detection and Protection

Publication details

Journal / source
Electrical Engineering
Volume
108
Issue
2
Publication date
9 January 2026
Language