Experimental analysis of multiple internal heat exchanger configurations in a Cascade refrigeration system using R290/R744

Read full text Summarise with VIRAT
Authors: Marwa Romdhane, Ramón Cabello, D Sanchez, Nihel Chekir
Cited by: 0
References: 31

Summary

No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.

Summarise with VIRAT Free to try with your Science Catalogs account.

Abstract

This paper addresses the global demand for sustainable, energy-efficient refrigeration by experimentally assessing the effect of internal heat exchangers (IHXs) on the performance of a vapour compression cascade refrigeration system (CRS) using R290 in the high-temperature cycle (HTC) and R744 in the low-temperature cycle (LTC). The CRS was equipped with three IHXs: one in the HTC (IHX 1 ), one in the LTC (IHX 3 ), and one linking the HTC's liquid line to the LTC's suction line (IHX 2 ). Tests covered all the possible IHX combinations and were performed under heat sink temperatures of 20 °C, 30 °C, and 40 °C, with a constant heat source temperature of −19 °C. Performance indicators, including COP, specific and volumetric cooling capacities, and specific compression work, are analysed. Results show that IHX integration improves energy efficiency across all configurations, with the greatest improvement (up to 11.17% at 20 °C) when IHX1, IHX2, and IHX3 are simultaneously activated, followed by the IHX 1 + IHX 3 configuration. The highest cooling capacity improvement (up to 7.1% at 20 °C) is achieved with the IHX1 + IHX3 configuration, followed by the IHX 1 + IHX 2 + IHX 3 configuration.

Fields of Study & Subjects

Refrigeration and Air Conditioning Technologies Adsorption and Cooling Systems Thermodynamic and Exergetic Analyses of Power and Cooling Systems

Publication details

Journal / source
Applied Thermal Engineering
Volume
297
Pages
130817–130817
Publication date
28 March 2026
Language
EN