Parametric optimization of PCM-enhanced underground thermal energy storage for buildings in moderate cold climates

Read full text
Authors: Ravi Anant Kishore, Chuck Booten, Tim J. LaClair, Matt Mitchell
Cited by: 1
References: 26

Abstract

This study presents a novel underground thermal energy storage (UTES) system designed for space heating in buildings located in moderate cold climates. The proposed UTES features a borehole with a depth of 25 ft. (7.62 m) and a diameter of 3 ft. (0.91 m), containing two helical pipe loops—one for discharge fluid and another for recharge fluid—and a thermally enhanced phase change material (PCM) layer that provides high energy storage capacity. The system requires daily thermal recharging using a low-grade heat source for a few hours and delivers continuous heating at a nearly constant discharge rate without significant performance degradation over a 24-h period. This study demonstrates that the optimized UTES, when recharged with hot fluid at an inlet temperature of 40 °C for 6 h daily, can provide a continuous heat discharge rate of approximately 2.9 kW for 24 h or 3.4 kW if operated under a shorter discharge period of 15 h (17:00–08:00). With a round-trip efficiency of 72–97%, the proposed UTES offers an efficient and reliable solution for short- and long-duration thermal energy storage technology, making it a promising technology for cold climates.

Fields of Study & Subjects

Geothermal Energy Systems and Applications Phase Change Materials Research Integrated Energy Systems Optimization

Publication details

Journal / source
Applied Thermal Engineering
Publisher
Elsevier BV
Volume
298
Pages
131068–131068
Publication date
17 April 2026
Language
EN