Localized diakoptic refactorization for MNA-based EMT and DP power system simulations

View at publisher
Authors: Christoph Wirtz, Simon Krahl, Albert Moser
Cited by: 0

Abstract

Electromagnetic-transient (EMT) as well as Dynamic-Phasor (DP) simulations of power system stability events using Modified Nodal Analysis (MNA) need repeated factorization of large sparse matrices whenever topology changes occur—such as short circuit faults, line protection tripping and voltage induced tripping of generators or loads. Traditional approaches rebuild the full system matrix at each event or precompute and factorize system matrices based on anticipated switching events. In this paper we propose a network tearing (diakoptics) approach that partitions the system into subnetworks, recomputing only the MNA blocks associated with topology changes. Previous studies have already shown that parallelizing simulation steps within the diakoptics framework can significantly improve performance. In this work, we show that diakoptics offers performance benefits even without parallelization, as only the matrix blocks affected need to be refactorized for topology changes. We validate our approach against full-system MNA solutions for both EMT and DP simulations and present results quantifying performance improvements and scalability across different network sizes and partitioning granularities.

Fields of Study & Subjects

Power System Optimization and Stability Real-time simulation and control systems Electromagnetic Simulation and Numerical Methods

Publication details

Journal / source
IET conference proceedings.
Volume
2025
Issue
45
Pages
180–184
Publication date
1 March 2026
Language
EN