Analysis of subsynchronous resonance of doubly-fed induction generator based on impedance modelling

View at publisher
Authors: Junye Chen, Micheal Schütt, Cord Prignitz, Andres Paez, Hans-Günter Eckel
Cited by: 0

Abstract

With the increasing integration of wind turbines, series capacitor compensation is widely used to improve transmission efficiency but raises the risk of sub-synchronous oscillations (SSO), especially in doubly fed induction generator (DFIG) systems. The slip-dependent rotor resistance can introduce a negative resistance effect on the stator side, potentially destabilizing the system. This study investigates the mechanisms of sub-synchronous resonance (SSR) in DFIG-based systems using mathematical modelling and impedance analysis. To enhance stability, a novel sub-synchronous stator flux injection method is proposed. This approach effectively reduces the equivalent mutual inductance, mitigating the stator-side influence of rotor-induced negative resistance and significantly improving damping performance. Impedance scanning and simulation results validate the theoretical findings, demonstrating that the proposed method provides a robust means to suppress SSR in series-compensated DFIG systems.

Fields of Study & Subjects

Wind Turbine Control Systems Power System Optimization and Stability Electric Motor Design and Analysis

Publication details

Journal / source
IET conference proceedings.
Volume
2025
Issue
45
Pages
718–724
Publication date
1 March 2026
Language