Transient Power Angle Stability of Fixed-Speed Pumped Storage Station Under Different Operating Conditions
Summary
No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.
Summarise with VIRAT Free to try with your Science Catalogs account.Abstract
Abstract In scenarios where a large-capacity fixed-speed pumped storage station (FS-PSS) is connected to the main power grid via long-distance transmission lines, the transient power angle stability of FS-PSS under generating and pumping conditions is susceptible to fault disturbances, with asymmetric short-circuit faults potentially causing more severe instability than symmetric ones. In this paper, a time-scale power angle stability model of the FS-PSS’s sending system is constructed to evaluate the electromagnetic power characteristics of FS-PSS under both generating and pumping operating conditions. Furthermore, the instability risk of FS-PSS under both symmetric and asymmetric faults is analysed deeply. Finally, the correctness of the theoretical analysis is verified through the simulations of the FS-PSS’s sending system.
Fields of Study & Subjects
Power System Optimization and Stability
Power Systems and Renewable Energy
Frequency Control in Power Systems
Publication details
- Journal / source
- Journal of Physics Conference Series
- Volume
- 3198
- Issue
- 1
- Pages
- 012028–012028
- Publication date
- 1 March 2026
- Language
- EN