Contact Bounce Characteristics of OLTC Vacuum Tube and Its Influence on Voltage-Current Characteristics Based on Electromechanical Coupling Modeling

Read full text Summarise with VIRAT
Authors: Gang Li, Ke Wang, Shuqi Zhang, Yao Zhang, Geqi Li, Ruijuan Tan, Ruoxi Wang
Cited by: 0
References: 7

Summary

No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.

Summarise with VIRAT Free to try with your Science Catalogs account.

Abstract

The on-load tap-changer (OLTC) is the core component of UHV converter transformer operation. During the switching process of the on-load tap changer, the action and bounce characteristics of the contact have an important influence on the breaking reliability and the life cycle operation stability of the on-load tap changer. At present, existing research mainly focuses on the overall switching characteristics and timing analysis of the on-load tap changer, while few studies address contact action and bounce behavior. In this paper, a nonlinear dynamic model of the collision contact between the moving and static contacts of the vacuum tube of the OLTC is established. The influence of the moving contact velocity and the contact mass on the contact bounce time and the number of bounces during the opening and closing process of the vacuum tube is analyzed, and the mechanical action process of the opening and closing of the vacuum tube is accurately described. To investigate the influence of mechanical bounce of the vacuum tube moving contact on electrical characteristics, and considering the approximately equal amount of heterogeneous charges at contact separation, a transient circuit model of the moving and static contacts based on electrical load characteristics is established. At the same time, the bounce characteristic curve obtained from the simulation results of the dynamic model is used as the boundary condition of the loop volt-ampere characteristic simulation, and the electrostatic force between the moving and static contacts and the dielectric polarization resistance analysis are introduced. The electromechanical coupling analysis model during the opening and closing process of the vacuum tube is proposed. The model introduces the vacuum interrupter closing command as the control condition, and is embedded in the overall switching transient circuit of the tap changer for analysis. The influence of the bounce phenomenon on the volt-ampere characteristics of the overall circuit of the tap changer is studied. The simulation results show that the number of bounces and the duration of bounce gradually decrease with the increase of the closing speed of the vacuum tube, and the increase of the mass ratio of the dynamic and static contacts can effectively suppress the electrical fracture phenomenon caused by the rebound of the static contacts. The volt-ampere characteristic curve of the whole switching transient circuit of the tap changer in the process of voltage level difference adjustment is given, and the abnormal protrusion phenomenon of the electrical waveform in the short time after the vacuum tube closing during the test is explained. The obtained model provides a theoretical basis for analyzing the electromechanical coupling dynamic load evolution of the OLTC and its influence on the switching performance.

Fields of Study & Subjects

Electrical Contact Performance and Analysis High-Voltage Power Transmission Systems Vacuum and Plasma Arcs

Publication details

Journal / source
Journal of Physics Conference Series
Volume
3198
Issue
1
Pages
012062–012062
Publication date
1 March 2026
Language
EN