Research on Fault Section Location Method of Distribution Network Coupled With ESMD and Energy Relative Entropy
Abstract
In accordance with power system operational standards, distribution networks are permitted to maintain operation for 1~2 hours following a single-phase grounding fault. However, such faults may escalate into multi-point grounding events, posing severe threats to system security and operational stability. Thus, accurate and rapid fault localization is essential to enable field personnel to promptly isolate faulty sections and restore normal power supply. This paper proposes a novel fault identification method that integrates Extreme-point Symmetric Mode Decomposition (ESMD), Energy Relative Entropy (ERE), and a fault judgment matrix. The method first employs ESMD to extract fault-induced features from transient voltage signals. It then utilizes a strategic configuration of Feeder Terminal Units (FTUs) to segment the network and identify the fault section. Finally, a fault judgment matrix is constructed to precisely locate the fault point within the identified section. Simulation results under various fault scenarios, including Gaussian white-noise and additional impulse noise interference, demonstrate the method's high accuracy and robustness, offering a reliable technical solution for fault diagnosis in distribution networks.