Starfish Optimization-Based Fractional Order 3DoF Control Strategy for Enhanced Frequency Stability in RES-Based Microgrids

Read full text
Authors: Imran Khan, Suheel Abdullah Malik, Amil Daraz, Muhammad Majid Gulzar, Baitullah Bareer
Cited by: 3
References: 77

Abstract

The frequency stability in microgrids presents vital challenges, due to unpredictable load variations and intermittent Renewable Energy Sources (RESs). This research investigates enhanced Load Frequency Control methodologies to address stability challenges from unpredictable loads and intermittent renewable energy integration in microgrids.Three Degree of Freedom Fractional order Tilted Integral Derivative Filter Cascaded One Plus Fractional Order Tilted Derivative Accelerator 3DoF-FOTIDN-(1+FOTDAγ) controller is tailored to stabilize frequency in microgrids integrating Photovoltaics (PVs), Wind Turbines (WTs), Fuel Cells (FCs), Electric Vehicles (EVs), Flywheel Energy Storage Source (FESS), Diesel Energy Generator (DEGs), Heat Pumps (HPs), and Controlled Redox Flow Batteries (CRFBs). Lyrebird Optimization Algorithm (LOA) and Walrus Optimization Algorithm (WOA) algorithms, and recently introduced Starfish Optimization Algorithm (SFOA) are employed to optimize the controller’s parameters. The Simulation outcomes reveal that the proposed controller with SFOA outperformed three Degree of Freedom-Proportional Integral Derivative (3DoF-PID), Fractional Order Tilted Integral Derivative Double Derivative squared (FOTIDD2), and Interval Type-II Fuzzy Fractional Order Proportional Derivative-Proportional Integral (IT2FFOPD-PI). The proposed strategy significantly minimized frequency excursion, fast settling, Overshoot (OSH), Undershoot (USH), and performance indices. The OSH is reduced by 99.77%, USH by 93.07%, Integral Absolute Error (IAE) by 99.20%, Integral Time-weighted Absolute Error (ITAE) by 98.96%, and Integral Squared Error (ISE) by 87.70%, with a settling time of 0.01345s. Furthermore, the controller is less sensitive to +40% parametric variations of the generator’s time constant (TG) with 8.43×10-6pu OSH and -7.892×10-4pu USH respectively. The integration of CRFBs further enhances system stability and resilience under dynamic and uncertain operating conditions.

Fields of Study & Subjects

Frequency Control in Power Systems Microgrid Control and Optimization Wind Turbine Control Systems

Publication details

Journal / source
IEEE Access
Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Volume
14
Pages
21312–21336
Publication date
1 January 2026