Waste-to-Energy-Coupled AI Data Centers: Cooling Efficiency and Grid Resilience

Read full text
Authors: Qi He, Chunyu Qu
Cited by: 9
References: 7

Abstract

AI data center expansion is increasingly constrained by grid interconnection capacity, driven in part by electricity-intensive cooling demand. This paper evaluates a coupled Waste-to-Energy (WtE) and AI data center configuration in which low-grade WtE thermal output drives absorption cooling, displacing grid-supplied cooling electricity. The system is modeled as a transparent input–output boundary and benchmarked against a conventional grid-powered cooling baseline. Results show that net grid-capacity relief is governed by three first-order factors: cooling coverage of IT heat load, parasitic auxiliary power, and distance-dependent thermal delivery losses. These factors define a break-even siting corridor beyond which capacity benefits vanish. The analysis shows that WtE-driven cooling can reduce grid imports under realistic conditions, enabling tighter integration of energy-generation resources with data centers.

Fields of Study & Subjects

Cloud Computing and Resource Management Distributed and Parallel Computing Systems Parallel Computing and Optimization Techniques

Publication details

Journal / source
2026 IEEE Green Technologies Conference (GreenTech)
Publisher
IEEE
Pages
1–6
Publication date
25 March 2026