Impedance-Based Stability Analysis of Droop-Controlled Inverters Considering the Inner Control, the Interlock Time, and RHP Poles

View at publisher
Authors: Robin Strunk, Pieris Sourkounis, Ludmila Ostuwar, Axel Mertens
Cited by: 0
References: 29

Abstract

This paper extends a previously developed impedance model of a grid-forming inverter. The model is described in the stationary αβ reference frame. The frequency coupling caused by the interlock time and the droop control is considered. Depending on the droop parameters and the operating point, the impedance model exhibits a pole in the right half-plane (RHP). A formula to approximate the location of this pole is proposed and it is considered in the impedance-based stability analysis of a microgrid with two grid-forming inverters. Laboratory measurements validate the impedance model and the stability analysis, but also reveal remaining limitations. The influence of the inner control on the stability is demonstrated by comparing a control design with a cascaded voltage and current control with an open-loop control approach. Additionally, asymmetric droop parameters and the influence of changes in the operating point are discussed.

Fields of Study & Subjects

Microgrid Control and Optimization Wind Turbine Control Systems Multilevel Inverters and Converters

Publication details

Journal / source
IEEE Journal of Emerging and Selected Topics in Power Electronics
Volume
14
Issue
2
Pages
1790–1803
Publication date
12 January 2026