A Nonlinear Adaptive Parameter Measurement Scheme for Resonant Grounded Distribution Networks

View at publisher
Authors: Tushar Kanti Roy, M. A. Mahmud
Cited by: 0
References: 17

Abstract

This paper presents a new scheme for measuring parameters in resonant grounded distribution networks (RGDNs) as these parameters significantly affect the fault compensation characteristics. The proposed adaptive scheme is developed based on the dynamical model of RGDNs with residual current compensation (RCC) inverters in which all parameters except the fault impedance is considered as unknown and parameter adaptation laws are designed to measure key parameters such as the leakage resistance, leakage capacitance, and inductance of the arc suppression coil. The proposed scheme also simultaneously compensates the fault behaviors through the RCC inverter as the desired fault compensation (i.e., the fault current and faulty phase voltage safe enough) is considered the basis for parameter measurement. The parameters are measured for different fault impedances to demonstrate the parameter measurement capability of the proposed adaptive scheme. Simulation results under different fault conditions with different initial values of key parameters in RGDNs clearly show that the proposed scheme accurately measures key parameters while achieving desired fault compensation.

Fields of Study & Subjects

Power Systems Fault Detection Power System Optimization and Stability Power Quality and Harmonics

Publication details

Journal / source
IEEE Control Systems Letters
Volume
10
Pages
271–276
Publication date
1 January 2026