Ineffective Calibration Testing of Residential Branch Circuit Breakers
Abstract
Previous test results demonstrated that some presently-marketed residential branch-circuit breaker brands have a double-digit defect rate. The defective breakers do not trip as required at 135% of rated current. The unique test results reported in this present paper clearly show that these calibration defects cannot be reliably detected by testing at 200% or 300% of rated current. One hundred defective breakers of three brands from the previous tests are retested. They all fail to trip at 135% of rated current, confirming that they are defective. The defective breakers then all pass the UL489 calibration test at 200% of rated current (must trip within 120 seconds), and they all also pass the NEMA AB4 calibration test at 300% of rated current (must trip within 50 seconds). These higher-current tests have a 100% error rate for detection of these improperly calibrated breakers. This explains how defective breakers come to be shipped from some factories. For some residential branch circuit breaker brands, ineffective testing - relying only on high-current calibration testing - has allowed defective breakers into the supply chain for many decades, increasing the risk of fire and injury for occupants of the buildings in which they are installed.
Fields of Study & Subjects
Electrical Fault Detection and Protection
Construction Engineering and Safety
Engineering and Technology Innovations