Bus Type Switching to Reduce Bound Violations in AC Power Flow

Read full text
Authors: Anna Van Boven, Kyri Baker
Cited by: 0
References: 18

Abstract

Wholesale power markets often use linear approximations of power system constraints. Because it does not consider inequality constraints, using AC power flow for feasibility post-processing can violate bounds on reactive power, voltage magnitudes, or thermal limits. There remains a need for a streamlined analytical approach that can guarantee AC feasibility while adhering to variable bounds. This paper suggests an augmented implementation of AC power flow that uses an additional two bus types (PQV and P) to help resolve voltage bound violations present in the traditional approach. The proposed method sacrifices the voltage setpoint at a generator in exchange for fixing the voltage at a load bus, thereby moving a degree of freedom around the network. Results on the IEEE 14-bus, 57-bus, and 300-bus test cases demonstrate how switching bus types can reduce overall network violations and help find feasible power system setpoints.

Fields of Study & Subjects

Power System Optimization and Stability Optimal Power Flow Distribution HVDC Systems and Fault Protection

Publication details

Journal / source
2026 IEEE Power & Energy Society General Meeting (PESGM)
Publisher
IEEE
Pages
1–5
Publication date
1 July 2026