Insulation Performance Analysis of Natural Ester Oil in 750kV Power Transformers

View at publisher Summarise with VIRAT
Authors: Huang Zhiqiang, Lan Liya, Cai Shengwei, Zhang Shurui, Li Jinbiao, Li Huaqiang
Cited by: 0
References: 7

Summary

No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.

Summarise with VIRAT Free to try with your Science Catalogs account.

Abstract

This study investigates the electric field characteristics, dielectric performance, and engineering feasibility of a 750 kV transformer insulated with natural ester oil. Electric field distributions in the high-voltage lead-out and transformer body are analyzed and compared for mineral oil and natural ester oil under power frequency conditions. Results show that natural ester oil exhibits slightly lower electric field strengths under AC conditions compared to mineral oil. Additionally, the analysis identifies areas of inadequate insulation margin in the transformer’s elevated structure, with proposed enhancements to optimize electric field distribution. Validation tests-including impulse voltage, AC withstand voltage, and partial discharge-demonstrate that the natural ester oil transformer complies with all standard requirements, supporting its applicability in engineering practice.

Fields of Study & Subjects

Power Transformer Diagnostics and Insulation High voltage insulation and dielectric phenomena High-Voltage Power Transmission Systems

Publication details

Journal / source
IEEE PES International Meeting (PES IM)
Pages
1–6
Publication date
18 January 2026