Analysis of Ferroresonance in Photovoltaic Park Distribution Systems

View at publisher
Authors: Mario Lopez-Albiter, V. Torres, Emmanuel Hernández-Mayoral, N. G. Cabrera
Cited by: 1

Abstract

Ferroresonance is a phenomenon of particular interest, characterized by causing temporary overvoltages in electrical systems, posing a risk to system integrity. Currently the increasing integration of renewable energy sources, such as wind and photovoltaic, generally implement distribution systems with underground cables interconnected trough transformers with different configurations, which increases the possibility of scenarios susceptible to the ferroresonance phenomenon. Since these overvoltage cause deterioration in the power quality and can damage to equipment. In this regard, this paper presents the modeling of photovoltaic park distribution system which connects the photovoltaic system through three winding transformers (Dy1y1) collecting the energy to transmit it through a power transformer connected to the 115 kV system, cable lengths are analyzed to determine the potential occurrence of the ferroresonance phenomenon under phase closing and opening conditions, in addition to evaluating the impact of maximum and minimum photovoltaic generation under system open conditions.

Fields of Study & Subjects

Magnetic Properties and Applications Magneto-Optical Properties and Applications Silicon and Solar Cell Technologies

Publication details

Journal / source
IEEE Latin America Transactions
Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Volume
24
Issue
6
Pages
612–620
Publication date
27 April 2026