Effect of air velocity and water temperature on a mechanical-draft cooling tower performance

View at publisher Summarise with VIRAT
Authors: Sampath Suranjan Salins, Shiva Kumar, S. V. Kota Reddy, Mahesh Raj Nagaraja
Cited by: 0

Summary

No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.

Summarise with VIRAT Free to try with your Science Catalogs account.

Abstract

Cooling towers are crucial in power plants and refrigeration, air conditioning & industrial processes. It can be natural or mechanical draft. Current work emphasizes on fabrication and performance analysis of a counterflow mechanical (induced) cooling tower. The cooling tower is built using Cellulose packing 7090 with a surface density of 632 m 2 /m 3 . Tests are done by varying the rate of air flow and the temperature of water. Results indicated that, as temperature of water rises from 50 to 80ºC, efficiency of the tower, its range, rate of heat flow and coefficient of performance rises by 19.40%, 70.91%, 181.91% and 90% respectively for flow rate of water equal to 3.5 LPM. Similarly, there is a drop in the tower efficiency by 3.89% when there is an increase in velocity of air. Results also yielded a rise on power consumption by 5.63% when velocity of air rises from 9–15 m/s.

Fields of Study & Subjects

Heat Transfer and Optimization Adsorption and Cooling Systems Refrigeration and Air Conditioning Technologies

Publication details

Journal / source
CRC Press eBooks
Pages
74–80
Publication date
25 March 2026
Language
EN
Document type
Book chapter