Influence of a Low-Temperature Refrigerator Scheme Solution Based on Environmentally Friendly Refrigerants on the Energy Efficiency of the Cycle

Read full text
Authors: Віктор Миколайович Козін, Serhii Sharapov, Hanna Barsukova
Cited by: 0
References: 14

Abstract

Introduction. Artificial cold at temperatures of –40 0C and below is widely used in various electrotechnological processes. At the same time, the choice of refrigerant and the configuration of the refrigeration cycle determine not only energy efficiency, but also the environmental safety of the system.Problem Statement. For deep-cold conditions, multi-stage or cascade circuits are typically applied, with a rational selection of refrigerant pairs to ensure high efficiency.Purpose. To assess the influence of the circuit design — given the environmental characteristics of refrigerants — on the energy efficiency of a low-temperature refrigeration cycle using the coefficient of performance (COP) and exergy efficiency (ε), and to provide practical recommendations for selecting both the circuit type and the refrigerants.Materials and Methods. A thermodynamic and exergetic comparative analysis of theoretical low-temperature refrigeration cycles has been performed. Numerical modeling has been carried out in REFPROP for specified temperatures (tc = 45 0C; tb = –45 0C). The analyzed schemes include: a two-stage vaporcompression refrigeration machine (VCRM) with an intermediate tank and coil; cascade systems for the refrigerant pairs R717/R13, R717/R23, R717/R290, R717/R744, and R717/R32; a modified cascade cycle; and a three-stage VCRM.Results. The highest energy efficiency (COP = 2.22; ε = 0.372) has been achieved using a three-stage R717 VCRM. Among conventional cascade refrigeration cycles, R717/R290 has been identified as the most energy-efficient (COP ≈ 2.00) and environmentally acceptable pair. The modifi d cascade cycle has de monstrated higher efficiency (COP ≈ 2.07) than conventional cascade schemes, and its implementation has enabled a notable reduction in thermomechanical parameters, positively affecting compressor service life.Conclusions. For low-temperature applications, multi-stage R717 VCRM systems should be preferred, as they have proven more energy-efficient than cascade circuits. When installation reliability is of primary importance, a modified cascade cycle with R717/R290 is advisable. For such a cycle, a rule for selecting the intermediate temperature has been proposed.

Fields of Study & Subjects

Refrigeration and Air Conditioning Technologies Thermodynamic and Exergetic Analyses of Power and Cooling Systems Advanced Thermodynamic Systems and Engines

Publication details

Journal / source
Science and innovation
Volume
22
Issue
1
Pages
94–106
Publication date
15 February 2026
Language
EN