Jana Nexus: Journal of Computer Science
Abstract
High-density AI data centers generate large heat loads while facing growing pressure to limit water use.Traditional evaporative cooling commonly requires 1.5-2.6 million gallons of water per megawatt each year.This paper presents the Multi-Stage Elevated Temperature Closed-Loop Architecture (MET-CLA), which combines direct-to-chip cold plates, dualstage coolant distribution units, staged dry coolers, and predictive control at coolant temperatures of 40-45 °C.A hybrid steady-state and transient thermal-fluid model, cross-checked against published elevated-temperature benchmarks, indicates that on-site Water Usage Effectiveness can be reduced to approximately 0.02-0.05L/kWh in temperate and hot-dry climates, while Power Usage Effectiveness remains in the range 1.06-1.12.The architecture is compatible with current high-power GPU platforms and is offered as a practical systems design for lower water intensity.
Fields of Study & Subjects
Energy Efficiency in Computing
Heat Transfer and Optimization
Cloud Computing and Resource Management
Publication details
- Journal / source
- Jana Nexus Journal of Computer Science
- Publication date
- 12 March 2026
- Language
- EN