Modeling and Power-Hardware-in-the-Loop Validation of Synchronous Machine Governor
Abstract
This paper introduces the development of a high-fidelity gas turbine governor model using a programmable logic controller for power-hardware-in-the-loop (PHIL) validation. The governor model is integrated with the National Renewable Energy Laboratory's (NREL) PHIL test bed, featuring a 2-MVA synchronous machine and a 2.5-MW variable-speed drive, to emulate NG-driven HRSGs and CTs under various operational scenarios. The primary objective of this research is to study the grid-connected and islanding operations of conventional generation sources, with representative startup sequences including turbine purge, ignition, speed ramp-up, synchronization, and breaker closure. Preliminary results of the generator governor model on NREL PHIL platform, particularly using the 2.5-MW dynamometer system, offered significant insights into the modeling techniques, hardware integration, scaling, and real-world simulation dynamics.
Fields of Study & Subjects
Real-time simulation and control systems
Power System Optimization and Stability
Microgrid Control and Optimization
Publication details
- Publication date
- 15 January 2026