How Inverter-Based Resources (IBRs) Affect Protection Relay Elements
Abstract
This presentation starts with the details of IEEE 2800-2022 requirements of IBR for balanced and unbalanced faults. Then, it shows how to design a droop based GFM control to be IEEE 2800-2022 compliant. An performance evaluation is carried out to see if three OEM GFM inverters 2800-2022 compliant or not. And finally we show how IEEE 2800-2022 complaint and non-compliant GFM inverter will impact the transmission line protection elements, such as directional element and FID. Finally, recommendations are made if the GFM is not IEEE 2800-2022 compliant to disable the protection elements that rely on reliable and regulated negative sequence current.
Fields of Study & Subjects
Power Systems Fault Detection
Islanding Detection in Power Systems
Power Quality and Harmonics