A study on the negative sequence current injection during LVRT of IBRsA

Read full text
Authors: A. Blazquez, M. Larruskain, E. Torres, P. Eguia, A. Castañon, ZIV. Spain, Roberto Cimadevilla, ZIV. Spain
Cited by: 0

Abstract

Low Voltage Ride Through (LVRT) behaviour of Inverter Based Resources (IBR) during asymmetrical grid faults is dictated by the requirements of Grid Code (GC) at the Point of Common Coupling (PCC) of the renewable energy plants. Earlier GCs demanded only positive sequence current injection, which gave freedom to inverter manufacturers to implement different negative sequence injection strategies, while newer GCs define specific negative sequence current injection requirements. The existence of different negative sequence current control strategies during grid faults creates problems for line protection relays, as fault detection algorithms malfunction for certain angle relationships between the negative sequence voltage and current phasors. This paper analyses different negative sequence injection algorithms of IBRs and demonstrates certain relationships between sequence impedances of the inverter that can be used for improving line protection algorithms. The analytical findings are confirmed via Real Time simulations of a Type 4 wind farm connected to a power system with different network strength characteristics. Key words. IBR, Grid Code, LVRT, Negative Sequence, Line Protection.

Fields of Study & Subjects

Power Systems Fault Detection Wind Turbine Control Systems Islanding Detection in Power Systems

Publication details

Journal / source
Renewable Energies Environment and Power Quality Journal
Volume
25
Issue
3
Pages
315–320
Publication date
1 February 2026