Research on Early Aging Fault Identification of Photovoltaic DC Combiner System

Read full text
Authors: Yu Zou, Kailong Chen, Huawei He, Zile Li, Jiaxun Teng
Cited by: 0
References: 13

Abstract

In order to detect typical faults in the photovoltaic Direct current (DC) system, this paper first compared and analyzed the frequency domain responses of two typical faults in the photovoltaic DC system at different insulation aging stages based on the early insulation aging theory and the insulation aging characteristics of DC transmission cables. A fault identification method based on the harmonic trajectory of the primary and secondary switch frequencies for pole-to-pole short-circuit faults was proposed. The feasibility of this fault identification method was verified through the controller algorithm and combined with the hardware experimental platform. This method utilizes basic mathematical theorems, and the code configuration is easy to implement. At the same time, adjusting the sliding-window coefficient and the threshold coefficient can change the sensitivity and false-alarm rate of the algorithm, achieving different levels of fault-identification accuracy and leading to the best results. A 90% accuracy and a false-alarm rate lower than 10% can be achieved, opening up new ideas and methods for photovoltaic fault identification. Experimental results show that this method has a fast fault identification speed, with an identification time ranging from 10 to 20 ms, and can achieve different levels of identification accuracy by flexibly adjusting the control parameters.

Fields of Study & Subjects

Electrical Fault Detection and Protection Power Systems Fault Detection HVDC Systems and Fault Protection

Publication details

Journal / source
Energies
Volume
19
Issue
5
Pages
1273–1273
Publication date
4 March 2026
Language
EN