Photovoltaic Sub-Synchronous Oscillation Suppression Method Based on Model-Free Adaptive Control

Read full text
Authors: Chaojun Zheng, Xiu Yang, Chenyang Zhao
Cited by: 1
References: 9

Abstract

The large-scale grid integration of photovoltaic systems, accompanied by extensive power electronic equipment, exacerbates the risk of sub-synchronous oscillation (SSO) and poses a serious threat to the safe and stable operation of modern power systems. To address the limitation that traditional additional damping controllers rely on accurate mathematical models of the system, this paper applies model-free adaptive control (MFAC) to suppress sub-synchronous oscillation in photovoltaic systems. The proposed method requires no prior identification of the plant model and achieves adaptive control by online estimation of pseudo-partial derivatives using only system input-output data, with parameters optimized by particle swarm optimization. Simulation results show that the proposed controller can effectively shorten the settling time and suppress oscillations However, for oscillations induced by different mechanisms, it still has the limitation of requiring parameter re-optimization. This approach provides a new model-free technical pathway for sub-synchronous oscillation mitigation in grid-connected photovoltaic systems.

Fields of Study & Subjects

Microgrid Control and Optimization Power System Optimization and Stability Photovoltaic System Optimization Techniques

Publication details

Journal / source
Energies
Publisher
MDPI AG
Volume
19
Issue
8
Pages
1977–1977
Publication date
19 April 2026