An Equivalent Model for Cooling Tower Boundary Conditions in Industrial Recirculating Cooling Water Systems

Read full text
Authors: Wei Huang, Yuehua Chen, Huokun Li, Zhongzheng He, li zhe, Bo Liu, Gang Wang
Cited by: 1
References: 6

Abstract

To mitigate the risks of pressure surges and water hammer during accidental pump trips in industrial cooling water systems, accurate boundary modeling of cooling towers is essential. This study employs the Method of Characteristics (MOC) to evaluate four equivalent models for the central riser shaft: Model A (constant level), Model B (two-way surge tank), Model C (dynamic coupling of shaft and distribution channel), and Model D (composite structure). Results indicate that Model A fails to reflect actual hydraulic states, producing an unrealistic pump reverse speed of −253.24 r/min and overly conservative estimates. While Models B, C, and D exhibit similar pressure trends, Model C most accurately captures the physical drainage process, realistically simulating how the shaft level stabilizes at the distribution channel elevation before declining. By accurately reflecting engineering hydraulics, Model C provides the most reliable basis for water hammer safety assessments. It is recommended for optimizing pump valve closure strategies, vacuum breaker installations, and siphon protection designs in power plant systems.

Fields of Study & Subjects

Water Systems and Optimization Nuclear Engineering Thermal-Hydraulics Hydraulic flow and structures

Publication details

Journal / source
Energies
Publisher
MDPI AG
Volume
19
Issue
10
Pages
2400–2400
Publication date
16 May 2026
Language
EN