An Evaluation Method for Partial Discharge in Generator Stator Bar Insulation Based on Fiber-Optic Acoustic Detection

Read full text Summarise with VIRAT
Authors: Jianlin Hu, Jiapeng Yang, Peiyu Qin, Xi Jiang, Wentao Luo
Cited by: 0
References: 25

Summary

No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.

Summarise with VIRAT Free to try with your Science Catalogs account.

Abstract

Partial-discharge (PD) monitoring is essential for assessing the insulation condition of generator stator bars. Conventional methods are susceptible to electromagnetic interference and are difficult to deploy in confined stator geometries. Fiber-optic acoustic detection technology offers strong immunity to electromagnetic interference and is suitable for the narrow and high-interference environment of stator bars, but it cannot directly provide discharge magnitude information. Therefore, in this study, fiber-optic acoustic detection technology was employed to acquire partial discharge acoustic signals from stator bars, and a mandrel-type fiber-optic acoustic sensor was developed, with PD tests performed on full-scale stator bars with internal defects. Meanwhile, considering the complex temporal characteristics of PD acoustic signals, a hybrid neural network-Transformer-convolutional neural network-long short-term memory (Transformer-CNN-LSTM)-was constructed for long-term time-series modeling to establish the mapping between acoustic signals and discharge magnitude intervals. The results indicate that fiber-optic acoustic detection enables sensitive and stable detection of weak PD acoustic signals. Phase-resolved PD (PRPD) patterns from the proposed system align with the discharge characteristics of internal defects, with the acoustic signal showing a phase lag relative to the electrical PD signal. The hybrid model achieved an overall interval estimation accuracy of 96.6%, outperforming CNN and CNN-LSTM models, with accuracies of 100% and 99.4% for discharge magnitude intervals below 100 pC and above 2000 pC, respectively.

Fields of Study & Subjects

High voltage insulation and dielectric phenomena Electrical Fault Detection and Protection Machine Fault Diagnosis Techniques

Publication details

Journal / source
Sensors
Volume
26
Issue
7
Pages
2053–2053
Publication date
25 March 2026
Language
EN