Impact of Evaporator Operating Mode Switching on the Performance of CO2 Commercial Refrigeration Systems

Read full text
Authors: Ionuț Dumitriu, Costel Ungureanu, Ion V. Ion
Cited by: 1
References: 23

Abstract

Commercial refrigeration systems represent some of the largest energy consumers in supermarkets, and therefore particular attention needs to be paid to increasing energy efficiency to reduce overall energy consumption and meet climate goals by 2030. This study investigates the performance of a CO2 (R744) commercial refrigeration system with evaporators operating alternately in dry and flooded modes. This operation is possible due to a particular adjustment using liquid sensors installed in the middle of both low-temperature (LT) and medium-temperature (MT) liquid separators, which transmit information to the controllers that regulate the compressor rack and evaporators, to switch from dry to flooded operation when the liquid level rises and vice versa when the level drops. The results show that the correct regulation of the system of 50% with 6K superheat operation and 50% with 3K superheat operation on MT evaporators, respectively, and 50% with 6K superheat operation and 50% with 4K superheat operation on LT evaporators leads to a reduction of energy consumption compared to 100% operation of all evaporators with 6K superheat by 6.9% per year for the compressor rack.

Fields of Study & Subjects

Refrigeration and Air Conditioning Technologies Thermodynamic and Exergetic Analyses of Power and Cooling Systems Heat Transfer and Optimization

Publication details

Journal / source
Technologies
Publisher
MDPI AG
Volume
14
Issue
7
Pages
436–436
Publication date
16 July 2026
Language
EN