Frequency-Modulated Disturbance Analysis of the Ferranti Effect in Low-Inertia Power Grids

Read full text
Authors: Pierpaolo Palazzo
Cited by: 1

Abstract

The Ferranti effect, i.e., receiving-end overvoltage on unloaded or lightly loaded long transmission lines, is regaining practical relevance in modern low-inertia power grids. This paper introduces an analytical framework that re-interprets the observed waveform dynamics at a point of interest-typically the receiving end-as an unintentional frequency modulation (FM) imposed on the nominal grid frequency carrier. By extracting the instantaneous frequency from the measured voltage via Hilbertbased processing, we define a compact scalar diagnostic index, the disturbance power P ∆f , which quantifies the "energy" of frequency deviations within short time windows. The approach is developed as a mathematical and inspectorial study: classical telegrapher-equation modeling provides the transmission-line basis, and theoretical/numerical examples illustrate how P ∆f can highlight dynamic severity beyond conventional magnitude-only indicators. The paper is intended as a first step toward experimental validation and collaboration on measurement chains and potential countermeasures, which are deliberately left outside the present scope.

Fields of Study & Subjects

Power Quality and Harmonics Power System Optimization and Stability Lightning and Electromagnetic Phenomena

Publication details

Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Publication date
10 February 2026
Document type
Preprint