Beyond Accuracy: Deployment-Facing Sensitivity Audits for Explainable Intrusion Detection in Industrial Control Systems (ICS)

Read full text
Authors: Heinrihs Kristians Skrodelis, Andrejs Romanovs
Cited by: 1
References: 39

Abstract

Industrial Control Systems (ICS) and SCADA networks underpin operational technology, yet intrusion detection system (IDS) research keeps reporting strong laboratory numbers while sidestepping deployment blockers—strict false-alarm budgets, real-time latency, nonstationary plant behavior. We present an operational sensitivity audit of an explainable hybrid IDS pipeline, treating windowing/stride, thresholding, and SHAP-based explanation generation as coupled components. On two labeled ICS datasets (CIC Modbus and TU Wien), 10 s to 30 s stride changes rarely flip attack-window decisions (2.15% and 3.87%), but on a benign-only IEC-104 trace the false-alarm rate jumps from 1.50 to 3.55 per hour—FAR is not stride-invariant. Global SHAP explanations stay stable under stride perturbation, yet decision-critical flip-window explanations do not (median cosine distance 0.161 on TU Wien). A KS drift detector flags an injected mean shift with zero pre-drift false alarms. Inference and fusion run sub-millisecond; every claim maps to a regenerable artifact.

Fields of Study & Subjects

Smart Grid Security and Resilience Adversarial Robustness in Machine Learning Network Security and Intrusion Detection

Publication details

Journal / source
WSEAS TRANSACTIONS ON SYSTEMS AND CONTROL
Publisher
World Scientific and Engineering Academy and Society (WSEAS)
Volume
21
Pages
43–43
Publication date
5 May 2026
Language
EN