DSP-Based Sub-Switching-Period Current-Limiting Control for Grid-Tied Inverter under Grid Faults
Abstract
This paper presents a sub-switching period current-limiting control for a grid-tied inverter to prevent transient overcurrents during grid faults and enable seamless fault ride-through (FRT). Sudden grid-voltage disturbances, such as voltage sags or phase jumps, can induce large transient currents within a switching period, particularly at low switching frequencies. Upon disturbance detection, the proposed method immediately modifies the pulse-width modulation carrier, enabling continuous regulation of the inverter output current within a time much shorter than a switching period without interrupting current flow. The proposed method can be implemented on commonly used digital signal processors without requiring specialized analog or digital circuits or high-speed computing devices. Experimental results from a 2-level, 3-phase inverter switching at 3.6 kHz validate the effectiveness of the proposed method under symmetric and asymmetric voltage sags and phase jumps.
Fields of Study & Subjects
Microgrid Control and Optimization
Multilevel Inverters and Converters
HVDC Systems and Fault Protection
Publication details
- Journal / source
- arXiv (Cornell University)
- Publication date
- 7 January 2026
- Document type
- Preprint