DSP-Based Sub-Switching-Period Current-Limiting Control for Grid-Tied Inverter under Grid Faults

Read full text
Authors: Jaeyeon Park, Jiyu Lee, Junyeol Maeng, Shenghui Cui
Cited by: 0

Abstract

This paper presents a sub-switching period current-limiting control for a grid-tied inverter to prevent transient overcurrents during grid faults and enable seamless fault ride-through (FRT). Sudden grid-voltage disturbances, such as voltage sags or phase jumps, can induce large transient currents within a switching period, particularly at low switching frequencies. Upon disturbance detection, the proposed method immediately modifies the pulse-width modulation carrier, enabling continuous regulation of the inverter output current within a time much shorter than a switching period without interrupting current flow. The proposed method can be implemented on commonly used digital signal processors without requiring specialized analog or digital circuits or high-speed computing devices. Experimental results from a 2-level, 3-phase inverter switching at 3.6 kHz validate the effectiveness of the proposed method under symmetric and asymmetric voltage sags and phase jumps.

Fields of Study & Subjects

Microgrid Control and Optimization Multilevel Inverters and Converters HVDC Systems and Fault Protection

Publication details

Journal / source
arXiv (Cornell University)
Publication date
7 January 2026
Document type
Preprint