Current and temperature imbalances in parallel-connected grid storage battery modules
Abstract
A key challenge with large battery systems is heterogeneous currents and temperatures in modules with parallel-connected cells. Although extreme currents and temperatures are detrimental to the performance and lifetime of battery cells, there is not a consensus on the scale of typical imbalances within grid storage modules. Here, we quantify these imbalances through simulations and experiments on an industrially representative grid storage battery module consisting of prismatic lithium iron phosphate cells, elucidating the evolution of current and temperature imbalances and their dependence on individual cell and module parameter variations. Using a sensitivity analysis, we find that varying contact resistances and cell resistances contribute strongly to temperature differences between cells, from which we define safety thresholds on cell-to-cell variability. Finally, we investigate how these thresholds change for different applications, to outline a set of robustness metrics that show how cycling at lower C-rates and narrower SOC ranges can mitigate failures.
Fields of Study & Subjects
Advanced Battery Technologies Research
Advancements in Battery Materials
Power Systems and Renewable Energy
Publication details
- Journal / source
- arXiv (Cornell University)
- Publication date
- 13 January 2026
- Document type
- Preprint