String-Level Ground Fault Localization for TN-Earthed Three-Phase Photovoltaic Systems

Read full text
Authors: Yuanliang Li, Xun Gong, Reza Iravani, Bo Cao, Heng Liu, Ziming Chen
Cited by: 1

Abstract

The DC-side ground fault (GF) poses significant risks to three-phase TN-earthed photovoltaic (PV) systems, as the resulting high fault current can directly damage both PV inverters and PV modules. Once a fault occurs, locating the faulty string through manual string-by-string inspection is highly time-consuming and inefficient. This work presents a comprehensive analysis of GF characteristics through fault-current analysis and a simulation-based case study covering multiple fault locations. Building on these insights, we propose an edge-AI-based GF localization approach tailored for three-phase TN-earthed PV systems. A PLECS-based simulation model that incorporates PV hysteresis effects is developed to generate diverse GF scenarios, from which correlation-based features are extracted throughout the inverter's four-stage shutdown sequence. Using the simulated dataset, a lightweight Variational Information Bottleneck (VIB)-based localization model is designed and trained, achieving over 93% localization accuracy at typical sampling rates with low computational cost, demonstrating strong potential for deployment on resource-constrained PV inverters.

Fields of Study & Subjects

Photovoltaic System Optimization Techniques Islanding Detection in Power Systems Power Systems Fault Detection

Publication details

Journal / source
arXiv (Cornell University)
Publication date
28 January 2026
Document type
Preprint