Hybrid Optimization of Grounding Grid Systems for UHV 1200 kV Transmission Lines

Read full text Summarise with VIRAT
Authors: Abderrahim El Asraoui, Ismail El Asraoui, Oumnia El Asraoui
Cited by: 0

Summary

No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.

Summarise with VIRAT Free to try with your Science Catalogs account.

Abstract

This paper presents a hybrid iterative optimization methodology for grounding grid systems in Ultra High Voltage (UHV) 1200 kV AC transmission corridors. The proposed approach combines rod addition, surface expansion, and depth increase strategies to achieve Z0/Z1 ratio compliance below 3.0 (IEEE C62.92) while maintaining Ground Potential Rise (GPR) under 50V (IEEE 80). Applied to a 1000 km, 8000 MW corridor, the algorithm converged in 26 iterations, reducing Z0/Z1 from 4.09 to 2.82 and GPR from 288V to 32V, with a final grounding resistance of 0.026 Ω.

Fields of Study & Subjects

High-Voltage Power Transmission Systems Lightning and Electromagnetic Phenomena Power Systems Fault Detection

Publication details

Journal / source
Zenodo (CERN European Organization for Nuclear Research)
Publication date
25 March 2026
Language
EN
Document type
Preprint