Analysis of Induced Voltage Due to AC Electromagnetic Effect in Metal Supporting Structures of 22.9kV Three-Phase Power Cables

View at publisher
Authors: Hyo-Jun Shin, Min-Woo Jeong, Hyeong-Jun Kim, Yong-Hee Kim, Chae-Won Kim, Se‐Hee Lee
Cited by: 0

Abstract

In power systems, cable arrangements strongly influence electrical, thermal, and spatial performance. Underground cables are typically installed in trefoil or flat configurations, with cleats placed at intervals to ensure stability under fault-induced electromagnetic forces. However, these arrangements may produce induced voltages and induced currents in the sheath, reducing reliability. Floating conductors, such as ungrounded cleats, can further enhance electromagnetic coupling and generate additional induced voltages. This study uses Finite Element Method (FEM) simulations on a cross-bonded trefoil cable model to analyze these effects. Results show that induced voltages arise from the combined action of electric and magnetic fields and are strongly affected by cleat conductivity. The findings indicate that induced voltages on floating conductors may accelerate insulation degradation and increase safety hazards, highlighting the need for proper cleat design and bonding practices.

Fields of Study & Subjects

High voltage insulation and dielectric phenomena High-Voltage Power Transmission Systems Electromagnetic Compatibility and Noise Suppression

Publication details

Journal / source
The Transactions of The Korean Institute of Electrical Engineers
Volume
75
Issue
2
Pages
356–361
Publication date
12 February 2026