Analysis of Series Arc Detection Using PCA

View at publisher
Authors: Min-Ho Yoon, Chan-Muk Park, Yu-Jung Cho, Sung-Hun Lim
Cited by: 0

Abstract

The risk of series arc faults presents a growing safety concern, as they are inherently undetectable by conventional overcurrent circuit breakers. This paper proposes a real-time series-arc detection technique based on principal component analysis(PCA). From current signals sampled at 100[kHz], we extract nine time-domain features once per 60[Hz] cycle (mean, variance, skewness, kurtosis, maximum, minimum, interquartile range, RMS, and peak-to-peak). These features are z-score standardized using parameters derived from a baseline of normal operational data and then projected onto the top three principal components. We define the Q-statistic (PCA residual variance) as the anomaly score and declare a series arc when it exceeds a predefined threshold for three consecutive cycles. Experiments show that incorporating RMS current variation enables reliable discrimination between series arcs and inrush currents demonstrating robust performance suitable for practical deployment.

Fields of Study & Subjects

Electrical Fault Detection and Protection Power Systems Fault Detection Power Quality and Harmonics

Publication details

Journal / source
The Transactions of The Korean Institute of Electrical Engineers
Volume
75
Issue
2
Pages
376–382
Publication date
12 February 2026
Language
EN