Identification of Oscillation Vulnerable Buses Using Reflection Coefficient
Abstract
The increasing penetration of renewable energy and power electronic devices has weakened grid strength by reducing system inertia and short-circuit capacity. In such weak-grid conditions, converter control loops interact with network impedance, causing oscillations across a wide frequency range from low-frequency to sub- and super-synchronous modes. This paper proposes an impedance-based reflection coefficient Γ method for the probabilistic pre-detection of oscillation-vulnerable buses before system disturbances occur. The method computes Γ from the system and load impedances at each bus and analyzes variations in its magnitude and phase with operating conditions (P,Q) Based on the Barkhausen stability criterion, buses showing abrupt phase changes are identified as oscillation-vulnerable points within the network. Simulation studies on the IEEE 39-bus using PSS/E verify the effectiveness of the proposed probabilistic pre-detection approach.
Fields of Study & Subjects
Power System Optimization and Stability
Microgrid Control and Optimization
Frequency Control in Power Systems
Publication details
- Journal / source
- The Transactions of The Korean Institute of Electrical Engineers
- Volume
- 75
- Issue
- 3
- Pages
- 472–480
- Publication date
- 13 March 2026
- Language
- EN