Using Sweep Frequency Response Analysis and Dissolved Gas Analysis in Diagnosing of Power Transformer

Read full text
Authors: Hoang Minh Vu Nguyen
Cited by: 0
References: 26

Abstract

This article presents two diagnostic techniques for assessing the mechanical and electrical condition of oil-immersed power transformers: sweep frequency response analysis (SFRA) and dissolved gas analysis (DGA). The SFRA method detects potential mechanical faults in transformer windings by applying the correlation coefficient (Rxy). For a 63 MVA, 115/23/11 kV transformer, experimental results show that the winding is considered normal when RLF ≥ 2.0, RMF ≥ 1.0, and RHF ≥ 0.6, whereas RLF < 0.6 indicates severe deformation. In contrast, the DGA method identifies internal faults such as partial discharge, low-energy and high-energy discharges, and thermal faults by analyzing gas concentrations in the insulating oil. For a 20 MVA, 110/22 kV transformer, measured gas concentrations (µl/l, ppm) include H₂ (0.00), CH₄ (40.43), C₂H₆ (18.24), C₂H₄ (20.92), C₂H₂ (0.00), CO₂ (8932.66), and CO (2131.18), corresponding to a “thermal fault below 300°C.” Both diagnostic methods are integrated into user-friendly MATLAB-based tools to support testing centers in Vietnam. The combination of SFRA and DGA enhances diagnostic accuracy, enables timely maintenance decisions, and contributes to improving the reliability of power supply systems.

Fields of Study & Subjects

Power Transformer Diagnostics and Insulation High voltage insulation and dielectric phenomena Machine Fault Diagnosis Techniques

Publication details

Journal / source
Technical Education Science/Giáo dục Kỹ thuật
Publication date
6 March 2026
Language
EN