Rancang Bangun Sistem Proteksi Otomatis pada Generator Turbin Gas dari Arus Berlebih dan Drop Tegangan Guna Meningkatkan Keandalan Operasional

Read full text
Authors: I Made Dody Permana, Antonius Edy Kristiyono, Achmad Dhany Fachrudin
Cited by: 0

Abstract

Gas turbine generators play an important role in providing electrical energy, especially in the maritime sector, but they are vulnerable to disturbances such as overcurrent and undervoltage, which can cause equipment damage. This study aims to design and test an automatic protection system based on the ESP32 microcontroller with the INA219 sensor to detect current and voltage, as well as a relay as a circuit breaker. The method used is an experimental approach including static and dynamic testing, both with and without a 5W AC lamp load as a simulation of real loading conditions. Test results show that the average sensor reading error is 2.65% for current and 1.76% for voltage, which is still within the ±3% tolerance limit. The system is able to disconnect the load when any parameter exceeds the protection threshold, although there are slight inconsistencies in the relay response due to sensor reading fluctuations. In conclusion, this automatic protection system is proven to be 85% accurate and responsive in maintaining the operational reliability of the gas turbine generator, making it applicable as a preventive solution against electrical disturbances in marine environments.

Fields of Study & Subjects

Power Systems Fault Detection Arduino and IoT Applications Electric Power Systems and Control

Publication details

Journal / source
JURAL RISET RUMPUN ILMU TEKNIK
Volume
5
Issue
1
Pages
750–761
Publication date
28 January 2026