Performance Prediction for Counter-flow Desiccant Wheels Using an Approximate Solution

View at publisher
Authors: Dong-Seon Kim, Dae-Young Lee
Cited by: 0

Abstract

An analytical model has been developed to predict the performance of desiccant wheels. This model is based on an approximate solution derived from a set of linearized governing equations, with the assumption that the desiccant temperature and moisture concentration change over time according to trigonometric functions. The model predicts the outlet conditions of air streams in a silica gel desiccant wheel under typical operating conditions, and the results are compared with those obtained from a numerical model. It is found that the maximum absolute error is ±1.5 K in dry bulb temperature and ±0.6 g/kg in humidity ratio within the ranges of 0.5≤Cr≤1, 1≤Ntu0≤5, 10-2≤Cr*≤10.

Fields of Study & Subjects

Adsorption and Cooling Systems Building Energy and Comfort Optimization Refrigeration and Air Conditioning Technologies

Publication details

Journal / source
설비공학논문집
Volume
38
Issue
1
Pages
26–40
Publication date
12 January 2026
Language