Analysis of a Two-Stage Thyristor Rectifier Topology with Parallel Bridges for Reactive Power Reduction

Read full text Summarise with VIRAT
Authors: Vasyl Komarov, Yu. V. Rassokhina
Cited by: 0
References: 20

Summary

No summary yet. VIRAT can read this paper and write a plain-language summary of its aim, methods, key findings and limitations.

Summarise with VIRAT Free to try with your Science Catalogs account.

Abstract

High-power phase-controlled thyristor DC drives, despite their reliability, have a fundamental drawback: significant reactive power consumption from the supply network, especially in dynamic operating modes with large firing angles (α). This leads to a low Displacement Power Factor (DPF) and additional losses. This study analyzes a cost-effective novel two-stage thyristor rectifier topology proposed to mitigate this problem. The topology utilizes a special transformer with secondary winding taps (e.g., at 50% and 100% voltage) that feed two 6-pulse bridges (R1 and R2), connected in parallel to a common DC load. The system functions as a high-speed solid-state equivalent of an On-Load Tap Changer (OLTC). By sequentially engaging the bridges, the converter maintains small firing angles (α) over a wide output voltage range. A detailed analysis of the energy characteristics, based on a case study of a typical acceleration cycle for a high-inertia drive (hoisting machine), demonstrates the topology's energy efficiency. Compared to a conventional single-bridge thyristor rectifier, the two-stage scheme reduces the total reactive energy consumed per acceleration cycle by 51% (from 54.4 kVAr · h to 26.8 kVAr · h in the example). An additional advantage of the solution is the reduction of the Root-Mean-Square (RMS) primary winding current during the initial acceleration stage, which leads to lower active power (I2R) losses in the transformer and supply lines. A drawback of the considered commutation algorithm is the presence of a 'discontinuous current mode' in the transformer primary winding during the mixed-mode (simultaneous operation of R1 and R2), which significantly degrades the harmonic spectrum (THD) of the input current, making the converter non-compliant with power quality standards (e.g., IEEE 519). The study concludes that practically implementing this energy-efficient topology requires hardware adaptation, specifically through the design of a custom Inter-Phase Reactor (IPR) or integration into multi-pulse configurations, to mitigate harmonic distortion while preserving the reactive power benefits.

Fields of Study & Subjects

Power Quality and Harmonics Electric Power Systems and Control Multilevel Inverters and Converters

Publication details

Journal / source
Вісник Національного технічного університету України Київський політехнічний інститут. Серія: Радіотехніка. Радіоапаратобудування
Issue
103
Pages
94–102
Publication date
30 March 2026
Language
EN