Refrigerant Charge Identification with Limited Data via Physics-Guided Semi-Supervised Regression
Abstract
Refrigerant leakage is the dominant fault responsible for the degradation of energy efficiency in vapor compression systems. To address this issue, a physics-guided semisupervised regression (PG-SSR) model is proposed, in which the refrigerant circulation rate derived from the energy conservation equation embedded into the neural network as guiding information. In addition, a joint pseudo-label generation mechanism is introduced by combining the maximum mean discrepancy (MMD) with MC Dropout to produce high-confidence refrigerant charge labels. This strategy leverages large amounts of unlabeled data to augment and enhance limited training samples, thereby enabling an accurate quantitative prediction of refrigerant charges under small-sample scenarios. Validation usinf experimental data from a split-type air conditioner demonstrated that under identical limited-sample conditions, PG-SSR reduced the root mean square error (RMSE) by 22.91 g (64.48%) and mean absolute percentage error (MAPE) by 3.86% (68.93%) compared with baseline models. These results highlight the synergistic benefits of physical guidance and jointly calibrated pseudo-labelling in improving refrigerant charge identification performance.
Fields of Study & Subjects
Refrigeration and Air Conditioning Technologies
Fault Detection and Control Systems
Building Energy and Comfort Optimization