Development and Experimental Validation of an Integrated Evaporative and Hybrid Air-Liquid Cooling System for Intelligent Computing Centers
Abstract
To address the heat dissipation challenges associated with high power density in intelligent computing centers, this study proposes an air-liquid dual source cooling system. The system utilizes a unified cold source with a stepwise water flow sequence of "air-cooling first, liquid-cooling second" to reduce exergy loss and match the temperature-grade of the respective cold source. The internal flow channel of the cooling unit was optimized through computational fluid dynamics simulations, and its performance was experimentally tested under high-temperature with high-humidity, moderate-temperature with moderate-humidity, and low-temperature conditions. Results indicate that the optimized unit achieves an outlet water temperature as low as 32.17 ℃ with a maximum coefficient of performance (COP) of 28.03 under high-temperature conditions. The unit also enables complete natural cooling under moderate conditions and reaches a peak COP of 33.4 under low-temperature conditions while maintaining stable operation. The system's overall approach degree ranges from 0.1 ℃ to 1.8 ℃, and its cooling capacity reaches 105.3%, outperforming the national standard. This study provides an efficient and practical cooling solution for high-density intelligent computing centers.
Fields of Study & Subjects
Adsorption and Cooling Systems
Heat Transfer and Optimization
Solar-Powered Water Purification Methods
Publication details
- Journal / source
- DOAJ (DOAJ: Directory of Open Access Journals)
- Publication date
- 1 February 2026
- Language
- ZH